THERMON Terminator ZP Power Connection Kit Instruction Manual
THERMON Terminator ZP Power Connection Kit

Receiving, Storing And Handling

  1. Inspect materials for damage incurred during shipping.
  2. Report damages to the carrier for settlement.
  3. Identify parts against the packing list to ensure the proper type and quantity has been received.
  4. Sungani pamalo ouma.

Zamkatimu

Zamkatimu

katunduyo kuchuluka Kufotokozera
1 1 Expediter Assembly
Support Cap with O-RingThreaded Grommet Compressor Grommet
Support Base with O-Ring
2 1 Junction Box Lid
3 1 Junction Box Base with O-Ring
4 1 mtedza
5 1 Zomangira
6 1 Banding Guide
7 1 Terminal Blocks with DIN Rail
(Refer to terminal specifications for maximum allowable wire size)
8 1 Junction Box Cord

Order Separately

PETK Power and End Termination Kits (per cable) 

PETK Power and End Termination Kits (per cable)

katunduyo kuchuluka Kufotokozera
1 1 RTV Tube
2 1 Power Connection Boot
3 1 Mapeto a Cap
4 1 Tape Strip 6″ (PETK-3 only)
5 1 End Termination Caution Label
6 1 GRW-G Grommet (PETK-3 only)
7 1 Ground Sleeve

miyeso

miyeso

Kusamalitsa Kukhazikitsa

  • To minimize the potential for arcing and fire caused by product damage or improper installation use ground-fault protection. The National Electrical Code (NEC) and Canadian Electrical Code (CEC) require ground-fault protection of equipment for each branch circuit supplying electric heat tracing.
  • Installation must comply with Thermon requirements and be installed in accordance with the NEC, CEC, or any other applicable national and local codes.
  • Component approvals and performance ratings are based on the use of Thermon specified parts only. User supplied power connection fittings must be listed or certified for intended use.
  • Avoid electrostatic charge. Clean only with a damp nsalu.
  • De-energize all power sources before opening enclosure.
  • Keep ends of heating cable and kit components dry before and during installation.
  • Individuals installing these products are responsible for complying with all applicable safety and health guidelines. Proper personal protective equipment, or PPE, should be utilized during installation. Contact Thermon if you have any additional questions.

Zida Zofunika

Zida Zofunika

Certifications/Approvals

Certifications/Approvals
P66/Type 4X -60°C ≤ Ta ≤ +55°C
Ordinary & Hazardous Locations
Class I, Division 2, Groups A, B, C, & D
Class II, Division 2, Groups F & G, Class III
Class I, Zone 1, AEx eb IIC T4-T6

unsembe Malangizo

  1. Locate bus connection (HPT and FP only) and cable as shown. Cut end of cable at angle to aid in piercing grommet. Leave additional cable for expansion loop. See page 5 for multiple cable installation tips
    unsembe Malangizo
  2. Insert cable into expediter. If mounted on bottom or side of pipe, punch out weep hole Note: For HPT and FP cable, exchange grommet in Terminator with GRW-G provided in PETK-3.
    unsembe Malangizo
  3. Slide expediter toward pipe and route cable through support base entry.
    unsembe Malangizo
  4. Insert banding guide into expediter and snap into place.
    unsembe Malangizo
  5. Mount expediter to pipe using pipe band. Do not band over cable.
    unsembe Malangizo
  6. Cut off end of cable
    unsembe Malangizo
  7. Terminate cable with appropriate PETK termination kit. Refer to PETK installation instructions.
    unsembe Malangizo
  8. Push excess cable back through expediter. Tighten cap securely. Tape cable expansion loop to pipe.
    unsembe Malangizo
  9. For power connection applications: Use dimple molded into side of junction box base to locate center of hole, drill for user supplied power connection fittings per manufacturer’s recommendations.
    unsembe Malangizo
  10. Mount junction box base on expediter. Make sure to align slots to properly orient junction box base. Tighten nut securely
    unsembe Malangizo
  11. For power connection applications: Install power connection fittings (user supplied) and pull in power and ground wires.
    unsembe Malangizo
  12. Install quick mount terminal blocks.
    unsembe Malangizo
  13. Complete system wiring. Refer to typical wiring details on page 5. Tightening torque 1.5 Nm– 1.8 Nm (1.1 ft-lb–1.3 ft-lb)
    unsembe Malangizo
  14. Install junction box lid and twist hand tight. Insert screwdriver into ratchet slots located on side of junction box base
    unsembe Malangizo
  15. Use screwdriver to ratchet on junction box lid. Lid will rotate 30 degrees.
    unsembe Malangizo
  16. Lid latch mechanism fully engaged. To remove lid, repeat steps 14 and 15 but in the opposite direction.
    unsembe Malangizo

Two Cable Layout Tips

Locate bus connection (HPT and FP only) and cable as shown. Cut end of cable at angle to aid in piercing grommet. Leave additional cable for expansion loop
Two Cable Layout Tips

Insert two cables into expediter.
Zindikirani: For HPT and FP cable, exchange grommet in Terminator with GRW-G provided in PETK-3.
Two Cable Layout Tips

Three Cable Layout Tips

Locate bus connection (HPT and FP only) and cable as shown. Cut end of cable at angle to aid in piercing grommet. Leave additional cable for expansion loop.
Three Cable Layout Tips

Insert three cables into expediter.
Zindikirani: For HPT and FP cable, exchange grommet in Terminator with GRW-G provided in PETK-3.
Three Cable Layout Tips

Mount expediter with three cables. Do not band over cable.
Three Cable Layout Tips

Typical Wiring Details

Power Connection (1 to 3 Cables). For 3 cable power connections, additional terminal blocks will be required when using 10mm2 (#8 AWG) power supply wiring
Typical Wiring Details

In-Line Splice and T-Splice
Typical Wiring Details

End Termination (1 to 2 Heating Cables) Remove jumpers for 2 cable terminations.
Typical Wiring Details

Support

Likulu la Mabungwe:

  • 100 Thermon Dr
  •  PO Box 609 San Marcos, TX 78667-0609
  • Phone: 512-396-5801
  • 1-800-820-4328
    Kuofesi ya Thermon yomwe ili pafupi ndi inu mudzatichezera ku . . . www.thermon.com
    Form No. PN50845-0320 © Thermon, Inc.
  • Wosindikizidwa ku USA
  • Zambiri zimatha kusintha.