NOTIFIER - chizindikiroSEP-SW(A), SEP-SPSW(A)
Dual Strobe Expander Plates for
Kulumikizana KwadzidzidziNOTIFIER XP6-R Six Relay Control Module

General

NOTIFIER’s XP6-R six-relay control module provides an intelligent fire alarm system with six Form-C relays.
The first module is addressed from 01 to 154 while the remaining modules are automatically assigned to the next five higher addresses. Provisions are included for disabling a maximum of three unused modules. A single isolated set of dry relay contacts is provided for each module address, which is capable of being wired for either a normally-open or normally-closed operation. The module allows the control panel to switch these contacts on command. No supervision is provided for the controlled circuit.
Each XP6-R module has panel-controlled green LED indicators.
The panel can cause the LEDs to blink, latch on, or latch off.

Mawonekedwe

  • Six addressable Form-C relay contacts
  • Removable 12 AWG (3.25 mm²) to 18 AWG (0.9 mm²) plug-in terminal blocks
  • Status indicators for each point
  • Unused addresses may be disabled
  • Rotary address switches
  • FlashScan® or CLIP operation
  • Mount one or two modules in a BB-XP cabinet (optional)
  • Mount up to six modules on a CHS-6 chassis in a CAB-3 Series, CAB-4 Series, EQ Series, or BB-25 cabinet (optional)
  • Zida zofunikira zikuphatikizidwa

zofunika

Standby current: 1.45 mA (SLC current draw with all addresses used; if some addresses are disabled, the standby current decreases)
Alarm current: 32 mA (assumes all six relays have been switched once and all six LEDs solid ON)
Kutentha kosiyanasiyana: 32°F mpaka 120°F (0°C mpaka 49°C)
Chinyezi: 10% mpaka 93% yosakondera
Dimensions: 6.8″ (17.27 cm) high x 5.8″ (14.73 cm) wide x 1.0″ (2.54 cm) deep
Shipping weight: 1.1 lb. (0.5 kg) including packaging Mounting options: CHS-6 chassis, BB-25 cabinet, BB-XP cabinet, CAB-3 Series (see DN-3549) cabinet, CAB-4 Series
(see DN-6857) cabinet, or EQ Series (see DN-60229) cabinet
Wire gauge: 12 AWG (3.25 mm²) to 18 AWG (0.9 mm²)
Maximum SLC wiring resistance: 40 or 50 ohms, panel dependent
Relay current: 30 mA/relay pulse (15.6 ms pulse duration), pulse under panel control
Relay contact ratings: 30 VDC; 70.7 VAC

Mavoti apano:

  • 3.0 A @ 30 VDC maximum, resistive, non-coded.
  • 2.0 A @ 30 VDC maximum, resistive, coded.
  • 1.0 A @ 30 VDC maximum, inductive (L/R = 2 ms), coded.
  • 0.5 A @ 30 VDC maximum, inductive (L/R = 5 ms), coded.
  • 0.9 A @ 110 VDC maximum, resistive, non-coded.
  • 0.9 A @ 125 VAC maximum, resistive, non-coded.
  • 0.7 A @ 70.7 VAC maximum, inductive (PF = 0.35), noncoded.
  • 0.3 A @ 125 VAC maximum, inductive (PF = 0.35), noncoded.
  • 1.5 A @25 VAC maximum, inductive (PF = 0.35), noncoded.
  • 2.0 A @25 VAC maximum, inductive (PF = 0.35), noncoded.

Ma Agency ndi Zovomerezeka

Mindandanda iyi ndi zovomerezeka zimagwira ntchito pamagawo omwe afotokozedwa mu chikalatachi. Nthawi zina, ma module kapena mapulogalamu ena sangatchulidwe ndi mabungwe ena ovomerezeka, kapena mindandanda ikhoza kuchitika. Funsani fakitale kuti mupeze mndandanda waposachedwa.

  • Mndandanda wa UL: S635
  • ULC Listed: S635 (XP6-RA)
  • MEA Listed: 368-01-E
  • CSFM: 7300-0028:0219
  • Maryland State Fire Marshall: Permit # 2099
  • FM Approved (Light Protective Signaling Only)

Chidziwitso cha Line Line

XP6-R: Six-relay control module
XP6-RA: Same as above with ULC Listing
BB-XP: Optional cabinet for one or two modules. Dimensions, DOOR: 9.234″ (23.454 cm) wide (9.484″ [24.089 cm] including hinges), x 12.218″ (31.0337 cm) high, x 0.672″ (1.7068 cm) deep; BACKBOX: 9.0″ (22.860 cm) wide (9.25″ [23.495 cm] including hinges), x 12.0″ (30.480 cm) high x 2.75″ (6.985 cm); CHASSIS (installed): 7.150″ (18.161 cm) wide overall x 7.312″ (18.5725 cm) high interior overall 2.156″ (5.4762 cm) deep overall
BB-25: Optional cabinet for up to six modules mounted on CHS-6 chassis (below). Dimensions, DOOR: 24.0″ (60.96 cm) wide x 12.632″ (32.0852 cm) high, x 1.25″ (3.175  cm) deep, hinged at bottom; BACKBOX: 24.0″ (60.96 cm) wide x 12.550″ (31.877 cm) high x 5.218″ (13.2537 cm) deep
CHS-6: Chassis, mounts up to six modules in a CAB-3 Series (see DN-3549), CAB-4 Series (see DN-6857), BB-25 cabinet, or EQ Series (see DN-60229) cabinet

Notifier® ndi chizindikiro cholembetsedwa cha Honeywell International Inc.
©2009 ndi Honeywell International Inc. Ufulu wonse ndi wotetezedwa. Kugwiritsa ntchito chikalatachi mosaloledwa ndikoletsedwa.

NOTIFIER ACT-2 Audio Coupling Transformer - icon 1

Chikalatachi sichinagwiritsidwe ntchito poyika.
Timayesetsa kusunga zinthu zathu zaposachedwa komanso zolondola.
Sitingathe kuphimba mapulogalamu onse kapena kuyembekezera zofunikira zonse.
Malingaliro onse atha kusintha osazindikira.
Kuti mudziwe zambiri, funsani Notifier. Foni: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com

NOTIFIER ACT-2 Audio Coupling Transformer - flgfirealarmresources.com

Zolemba / Zothandizira

NOTIFIER XP6-R Six Relay Control Module [pdf] Buku Logwiritsa Ntchito
XP6-R Six Relay Control Module, XP6-R, Six Relay Control Module, Six Relay Module, Control Module, Relay Module, Relay, Module

Zothandizira

Kusiya ndemanga

Anu email sati lofalitsidwa. Amafuna minda amalembedwa *